Full Port Ball Valves / Model T-1002 and S-1002
Valve Category:
Ball Valves
Valve Subcategory
Full Port
Manufacturer
Legend Valve
- Forged Brass
- Gland Follower Stem Design
- I.P.S. and CxC
- ISO-9002
LEGEND MODELS T-1002/S-1002 ball valves are constructed of heavy duty
forged brass. They are designed for residential, commercial and industrial use
on steam, water, oil or gas. Their full ports allow for a maximum of flow and a
minimum of pressure drop or turbulence. The stem is sealed with an adjustable
gland follower and is a blowout proof design.
CONFORMS TO FEDERAL SPECIFICATION WW-V-35C
- CSA certified for use with natural, manufactured, mixed, liquified petroleum and L.P. gas/air mixtures:
- ANSI standard Z21.15 for use as a gas appliance connector valve for 1/2-lb. systems. (1/2"-2")
- CSA certified 3-88 for use in 2 or 5 lb. house piping systems.(1/2"-2")
- ANSI/ASME B16.33 for use in gas piping systems up to 125 PSIG. (1/2"-2')
- U.L. listed 2J73 for L.P., natural and manufactured gases; flammable liquids; No. 6 oil at 250F. (1/2"-2")
- Factory Mutual approved for fire protection service. (1/2"-2")
CONFORMS TO FEDERAL SPECIFICATION WW-V-35C
PRESSURE RATING 1/4-2 600 W.O.G. NON-SHOCK 21/2-3 400 W.O.G. NON-SHOCK All sizes rated: 150 W.S.P. |
Request a Quote | Request Quote |
MATERIAL SPECIFICATION | |
PART | MATERIAL |
HANDLE NUT | STEEL |
HANDLE | STEEL |
PACKING NUT | FORGED BRASS |
STEM PACKING | PTFE |
STEM | FORGED BRASS |
BALL | CHROME PLATED BRASS |
SEATS | PTFE |
BODY | FORGED BRASS |
END ADAPTER | FORGED BRASS |
DIMENSIONS IN INCHES | ||||||
VALVE SIZE | A (I.P.S.) | A (CxC) | B | C | D | C.V.** |
1/4 | 1.81 | - | 1.46 | .39 | 3.31 | 6.5 |
3/8 | 1.81 | 1.62 | 1.46 | .39 | 3.31 | 6.5 |
1/2 | 2.01 | 1.93 | 1.54 | .50 | 3.31 | 10 |
3/4 | 2.36 | 2.76 | 1.89 | .79 | 4.65 | 26 |
1 | 2.88 | 3.31 | 2.05 | 1.00 | 4.65 | 48 |
11/4 | 3.31 | 3.78 | 2.52 | 1.26 | 5.28 | 70 |
1 1/2 | 3.63 | 4.30 | 2.72 | 1.50 | 5.28 | 105 |
2 | 4.22 | 5.32 | 3.47 | 2.00 | 7.88 | 200 |
21/2 | 5.16 | 6.97 | 3.86 | 2.48 | 7.88 | 380 |
3 | 5.91 | 7.91 | 4.17 | 2.95 | 7.88 | 520 |
**The CV Factor is the gallons of water per minute passed through the valve with
a 1 PSI pressure drop.